Refrigeration Valve Stations- PVS | #PVS4W8S8L6X1B7NHAXSTAXST


LOADING IMAGES
PVS4W8S8L6X1B7NHAXSTAXST

Refrigeration Valve Stations- PVS | #PVS4W8S8L6X1B7NHAXSTAXST

2 PVS4-A4D RAA HV


Especificaciones técnicas

  • Opciones: No Tamper Proof
  • Tipo de conexión: SW 2 "
  • Punto de referencia de presión alta: Factory Setting
  • Material de la válvula: Plated
  • Rango de control de presión: 0.35 to 10 Bar (5-150 psig)
  • Opción especial: Dual Pressure Regulator, Regulator Range 0.35-10 bar (5-150 psi)
  • Tamaño del puerto: 50 mm (2 ")
  • Opciones adicionales: No Tamper Proof
  • Tipo de tamiz: HV/Strainer
  • Número de posiciones: 4.0
  • Posición final: Hand Valve
  • Punto de referencia de presión baja: Factory Setting
  • Tipo de bobina: 120/60 DIN, Standard
  • Método de control: Duel Inlet Regulator, No Regulator Variation
  • Conector de capacidad: Full
  • Posición 4: N/A
Safety Warning

Información del artículo

The PVS is an innovative design which combines several different functions into one compact valve station. It was designed for simplified installation as well as to overcome corrosion issues encountered in harsh environments by utilizing plated and stainless steel components. Being weld-in, the valves reduce potential for connection leaks. Since all the shut-off and control valves are top mounted the PVS can be easily serviced with standard tools.

Markets:
• Industrial Refrigeration

Features and Benefits:
• Suitable for ammonia, CO2 and other common refrigerants
• Features multiple functions in a single housing
• Plated steel housing increases product life cycle
• Overall weight reduction up to 50% compared to traditional flanged products
• Interchangeable with other P-Series Offerings
• Coil options to meet various applications
• Serviceable from the top using standard tools
• Top mounted shut-off valves eliminates service issues
• Lock out seal caps
• Complies with ASME B31.5 and 16.34, PED 2014/68/EU
Function and Design:
• Multi- module platform available in four or five port housings, with the capability of interchangeable modules:
o Isolation Valve (hand shut- off)
o Strainer (100 Mesh)
o Solenoid
o Regulator
o Electronic Valve (PEV)
o Electronic Expansion
o Hand Expansion
o Stop/ Check

Application:
• Evaporator Control Groups
o Relief Regulation
o Suction Regulation
o Pumped Liquid Feed
o Hot Gas Defrost
• High Pressure Liquid Solenoid

Leer más Mostrar menos

Diseños en CAD + Archivos

No hay archivo CAD disponible

OK

x

Documentos relacionados

×


Encontrar un distribuidor

Puntos de venta

Contacto local

Parker Hannifin Corporation

Refrigerating Specialties Division

2445 South 25th Avenue

Broadview, IL 60155 USA

Teléfono

+1 (708) 681-6300

Fax

+1 (708) 681-6306

Consiga su cuenta de Parker hoy mismo!

Cree una cuenta para gestionar todo lo que haga con Parker, desde sus preferencias de compra hasta su acceso a la aplicación.

687PDC
687475