Liquid Level Wire Probe- HBLT- Wire

Liquid Level Wire Probe- HBLT- Wire

The HBLT-WIRE is a field adjustable capacitive liquid level sensor designed to measure refrigerant levels in traditional stationary systems such as vessels, receivers or accumulators, as well as in marine systems.

Especificaciones técnicas

  • Número de modelo: Please Configure Part for Model Number
  • Tamaño de la conexión: 3/4 inch (NPT), 1 inch (BSP)
  • Presión de trabajo máxima: 100 barg, 100 bar, 1450 psig
  • Longitud mínima de sonda ajustable: 300 mm, 12 inch
  • Longitud máxima de sonda ajustable: 4000 mm, 157 inch
  • Rango de alarma: 10% to 100%
  • Temperatura mínima del líquido: -50 °C, -58 °F
  • Temperatura máxima del líquido: 100 °C, 212 °F
  • Temperatura ambiente mínima: -30 °C, -22 °F
  • Temperatura ambiente máxima: 50 °C, 122 °F
  • Máxima resistencia de carga eléctrica: 500 Ohm
  • Conexión eléctrica: M12, 5 Pin - 5 m (196") Long
  • Salida de señal: 4-20mA (0-100%)
  • Tipo de salida: PNP, Solid State- 1A
  • Voltaje de entrada: 24 VAC ±10%
  • Voltaje de suministro eléctrico: 24V VDC ±10%
  • Frecuencia: 50/60 Hz
  • Consumo de energía: 1.5 W
  • Tipo de carcasa: IP65
  • Cumplimiento con especificaciones: EMC Emission EN61000-3-2, EMC Immunity EN61000-4-2, GOST-R No. 0903044, GOST-R No. 0903045

Descripción completa del producto

Better, compact and cost efficient, the HBLT-Wire is a field adjustable capacitive liquid level sensor designed to measure refrigerant levels in traditional stationary systems such as vessels, receivers or accumulators, as well as in marine systems.
The HBLT-Wire is an all-in-one length probe. The flexible sensor wire provides on the job length adjustability, so one part number covers all application requirements. The sensor has an output signal of 4-20 mA, which is proportional to the 0 and 100% of liquid level.

Markets:
• Industrial Refrigeration
• Commercial Refrigeration

Product Features:
• Suitable for ammonia and halocarbon refrigerants
• Adjustable length: Cut and configure wire from 300 to 400 mm (12 to 157 in)
• No requirement for recalibration or dead zone optimization, "Plug and Play"
• Configure and calibrate using a free Windows utility
• Electronic head and probe can be separated without emptying the vessel, "Service Friendly"
• One alarm output available
• Physically backwardly compatible with Refrigerating Specialties Depth Probe Tracker and ELL probe models
• Can be used without controller for basic level control

Application:
• Vessles
• Receivers
• Accumulators
• Marine Systems